Troubleshooting
TS05-ODU: Open circuit or short circuit of outdoor temperature sensor(T3, T4, TP, T2B,TH)
diagnosis and solution
Description
: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Sensors
• Outdoor main PCB
Troubleshooting and repair:
Check the connection between
temperature sensor and PCB.
Replace the outdoor main PCB
Is it within acceptable
parameters?
Is it properly wired?
Ensure proper connections.
NO
Measure the resistance value
of the sensor.
YES
Replace the sensor.
NO
YES
Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric control
box should be replaced as a whole. For certain models, outdoor unit uses combination sensor, T3,T4 and TP are
the same of sensor. This picture and the value are only for reference, actual appearance and value may vary.