2. Pipe Length and Drop Height
The length and elevation of connection pipe are shown in the table below. if the pipe length exceeds max pipe length,
additional refrigerant should be charged to ensure nominal cooling/heating capacity.
Capacity(Btu/h)
Standard Length
Max Pipe Length
Max Elevation
Additional Refrigerant
48k
5m (16.4ft)
65m(213.25ft)
30m(98.4ft)
24g/m (0.26oz/ft)
If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil
traps in the rising gas pipe can prevent this.
-An oil trap should be installed every 6m(20ft) of vertical suction line riser (
<
36000Btu/h unit).
-An oil trap should be installed every 10m(32.8ft) of vertical suction line riser (≥36000Btu/h unit).
10m/32.8ft (≥36000Btu/h unit)
6m/20ft (
<
36000Btu/h unit)
10m/32.8ft (≥36000Btu/h unit)
6m/20ft (
<
36000Btu/h unit)
Indoor unit/
Outdoor unit
Indoor unit/
Outdoor unit
Specifications 3