MOST IMPORTANT PARAMETERS TO BE SET BY THE INSTALLER
We remember that:
- parameters
dFA e dSA
are factory set and must not be changed by the installer/customer, iif not agree with the manufacturer of the warm air
heater
- parameter
rtC
real time must be set by the installer
- parameters
SLP, dAy, nlt and relevant ambient temperature Set Point T
, winter, summer, day, night : can be modified b the installer,
from the default value factory set, see table of parameters.
In order to set/ verifie the parameters procede as follows:
. SETPOINT for ambient temperature T: depending on different function modes
dAy, nlt
, several temperature Set Point T are factory set, you can
see on display SMALL ( 11, fig. 3 ). To reset/change press SET for more than 5 seconds, for enter the parameter’s menu.
To scroll the various parameters, use
. When on a parameter, to modifie press
SET
, than modifie with and confirm by pressing the
SET
button again. For the current parameter on display is possibile change it directly with . .To exit the parameters menu, press the
PRG
button.
Ambient temperature factory Set Point are:
- Set winter day ( default 20.0°C) and night ( default 18°C, minimum setting temperature 10°C)
CLOCK, TIME BANDS
Press button
PRG:
parameter
rtC
is show; to scroll the various parameters, use
. When on a
parameter, to modifie press
SET
, than modifie with
and confirm by pressing the
SET
button again. To exit the parameters menu,
press the
PRG
button.
Parameters to verifie/reset are:
code
parameter
Factory set
rtC
clock hh.min
dAy
start day band
Default 08:00
nlt
start night band
Default 20:00
SLP
manual changeover duration between
dAy
and
nlt
Default 8 hours
To disable the time bands function, set parameter
rtC
OFF, as follows: press the
PRG
button, select parameter
rtC
, and change his value into
00:00, than press once more with
to select OFF and press SET to confirm.
By parameter
rtC
OFF the function mode is allways day, and only day Set Points are operating; the night Set Points will be operating only by
pressing button
, change of status manual.
SLP
manual changeover duration between
dAy
day band and
nlt
night band. To change this duration, press
PRG
and scroll to display
SLP
.
Press
SET
and with modifie
SLP
value;
or eliminate it, down to OFF. Press
SET
to confirm. To exit the parameters menu, press the
PRG
button.
After time bands are set, simbol CLOCK will appear on display.
The
“CLIMA”
regulator is ready. To start operate press
ON
.
For more information on the regulator
“CLIMA”,
consult the general Clima CAREL manual on web site: www.carel.com and go on the type
ADCA000110