Fig.8 Trap with closed piping and trap with open piping
Condensing water produced by "L" Series warm air heater
Mod.
30
60
80
100
150
175
200
250
300
425
500
600
Condensing
water lt/h
0,5 1,85 0,5
0,5
2
3,5
3
6
5
8,5
9
9
ASSEMBLY OF DIRECT AIR DELIVERY PLENUM
The plenum, if any, must be assembled as described on chapter
PLENUM
of this manual; it is recommended to apply
silicone sealant on contact surfaces.
In the standard version, the plenum is provided with grilles on three sides and adjustable horizontal/vertical fins.
Make sure the air delivery fins are not too inclined, for their capacity and delivery would be reduced.
INSPECTIONS ON FIRST START-UP
Check :
Ø
the performance of burner RX and make sure that the emissions of CO2, CO and Nox do not exceed the pre-
determined tolerances, as shown in the table on Chapter
DATA SHEET
. Consul the manual of the RX burner,
delivered together with this warm air heater.
Ø
Visually check that the burner flame is regular and does not hit the bottom of the combustion chamber.
Ø
Check that the direction of rotation of the fan(s) is the one indicated by the arrow on the impeller (see fig.)
Ø
Check motor absorption by means of ammeter and make sure it does not exceed the values specified on
Chapter
DATA SHEET
.
Ø
Check the performance of heater thermostats: FAN, LIMIT and LIMIT2 (see Chapter
TRI-THERMOSTAT
)
Ø
Perform a combustion analysis
Ø
Prepare a power station or plant handbook and record the information required to be disclosed pursuant to
the laws, rules, regulations and standards in force
.