8
Technical Information
!
Note:
• The through-wall height of drain hose shouldnt be higher than
the outlet pipe hole of indoor unit.(As show in Fig.25)
• Slant the drain hose slightly downwards. The drain hose cant be
curved, raised and fluctuant, etc.(As show in Fig.26)
• The water outlet cant be placed in water in order to drain
smoothly.(As show in Fig.27)
2
.7 VACUUM PUMPING AND LEAK
DETECTION
1. Use Vacuum Pump
a. Remove the valve caps on the liquid valve and gas valve and
the nut of refrigerant charging vent.
b. Connect the charging hose of piezometer to the refrigerant
charging vent of gas valve and then connect the other
charging hose to the vacuum pump.
c. Open the piezometer completely and operate for 10-15min
to check if the pressure of piezometer remains in -0.1MPa.
d. Close the vacuum pump and maintain this status for 1-2min
to check if the pressure of piezometer remains in -0.1MPa. If
the pressure decreases, there may be leakage.
e. Remove the piezometer, open the valve core of liquid valve
and gas valve completely with inner hexagon spanner.
f. Tighten the screw caps of valves and refrigerant charging
vent.(As show in Fig.28)
50
Installation and Maintenance
Service Manual
(3) The water outlet cant be placed in water in order to drain
smoothly.(As show in Fig.27)
Liquid valve
Gas valve
Refrigerant charging
vent
Nut of refrigerant
Charging vent
Vacuum pump
Piezometer
Valve cap
Lo
Hi
Inner hexagon
spanner
Open
Close
The drain hose can't be fluctuant
The drain hose
can't be fluctuant
The water
outlet can't be
fluctuant
The water outlet
can't be placed
in water
1. Use Vacuum Pump
(1) Remove the valve caps on the liquid valve and gas valve
and the nut of refrigerant charging vent.
(2) Connect the charging hose of piezometer to the refrigerant
charging vent of gas valve and then connect the other charging
hose to the vacuum pump.
(3) Open the piezometer completely and operate for 10-15min
to check if the pressure of piezometer remains in -0.1MPa.
(4) Close the vacuum pump and maintain this status for 1-2min
to check if the pressure of piezometer remains in -0.1MPa. If
the pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve
and gas valve completely with inner hexagon spanner.
(6) Tighten the screw caps of valves and refrigerant charging
vent.(As show in Fig.28)
1. Check after Installation
Check according to the following requirement after finishing
installation.
2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 60.8°F, the air
conditioner cant start cooling.
2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air
bubbles coming out of this position, theres a leakage.
8.7 Vacuum Pumping and Leak
Detection
8.8 Check after Installation and Test
Operation
Fig.26
Fig.27
Fig.28
(1) The through-wall height of drain hose shouldnt be higher
than the outlet pipe hole of indoor unit.(As show in Fig.25)
(2) Slant the drain hose slightly downwards. The drain hose
cant be curved, raised and fluctuant, etc.(As show in Fig.26)
Note:
NO.
Items to be checked
Possible malfunction
1
Has the unit been
installed firmly?
The unit may drop, shake or
emit noise.
2
Have you done the
refrigerant leakage test?
It may cause insufficient cooling
(heating) capacity.
3
Is heat insulation of
pipeline sufficient?
It may cause condensation and
water dripping.
4
Is water drained well?
It may cause condensation and
water dripping.
5
Is the voltage of power
supply according to the
voltage marked on the
nameplate?
It may cause malfunction or
damage the parts.
6
Is electric wiring and
pipeline installed
correctly?
It may cause malfunction or
damage the parts.
7
Is the unit grounded
securely?
It may cause electric leakage.
8
Does the power cord
follow the specification?
It may cause malfunction or
damage the parts.
9
Is there any obstruction
in air inlet and air outlet?
It may cause insufficient cooling
(heating) capacity.
10
The dust and
sundries caused
during installation are
removed?
It may cause malfunction or
damaging the parts.
11
The gas valve and liquid
valve of connection pipe
are open completely?
It may cause insufficient cooling
(heating) capacity.
12
Is the inlet and outlet
of piping hole been
covered?
It may cause insufficient cooling
(heating) capacity or waster
eletricity.
50
Installation and Maintenance
Service Manual
(3) The water outlet cant be placed in water in order to drain
smoothly.(As show in Fig.27)
Liquid valve
Gas valve
Refrigerant charging
vent
Nut of refrigerant
Charging vent
Vacuum pump
Piezometer
Valve cap
Lo
Hi
Inner hexagon
spanner
Open
Close
The drain hose can't be fluctuant
The drain hose
can't be fluctuant
The water
outlet can't be
fluctuant
The water outlet
can't be placed
in water
1. Use Vacuum Pump
(1) Remove the valve caps on the liquid valve and gas valve
and the nut of refrigerant charging vent.
(2) Connect the charging hose of piezometer to the refrigerant
charging vent of gas valve and then connect the other charging
hose to the vacuum pump.
(3) Open the piezometer completely and operate for 10-15min
to check if the pressure of piezometer remains in -0.1MPa.
(4) Close the vacuum pump and maintain this status for 1-2min
to check if the pressure of piezometer remains in -0.1MPa. If
the pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve
and gas valve completely with inner hexagon spanner.
(6) Tighten the screw caps of valves and refrigerant charging
vent.(As show in Fig.28)
1. Check after Installation
Check according to the following requirement after finishing
installation.
2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 60.8°F, the air
conditioner cant start cooling.
2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air
bubbles coming out of this position, theres a leakage.
8.7 Vacuum Pumping and Leak
Detection
8.8 Check after Installation and Test
Operation
Fig.26
Fig.27
Fig.28
(1) The through-wall height of drain hose shouldnt be higher
than the outlet pipe hole of indoor unit.(As show in Fig.25)
(2) Slant the drain hose slightly downwards. The drain hose
cant be curved, raised and fluctuant, etc.(As show in Fig.26)
Note:
NO.
Items to be checked
Possible malfunction
1
Has the unit been
installed firmly?
The unit may drop, shake or
emit noise.
2
Have you done the
refrigerant leakage test?
It may cause insufficient cooling
(heating) capacity.
3
Is heat insulation of
pipeline sufficient?
It may cause condensation and
water dripping.
4
Is water drained well?
It may cause condensation and
water dripping.
5
Is the voltage of power
supply according to the
voltage marked on the
nameplate?
It may cause malfunction or
damage the parts.
6
Is electric wiring and
pipeline installed
correctly?
It may cause malfunction or
damage the parts.
7
Is the unit grounded
securely?
It may cause electric leakage.
8
Does the power cord
follow the specification?
It may cause malfunction or
damage the parts.
9
Is there any obstruction
in air inlet and air outlet?
It may cause insufficient cooling
(heating) capacity.
10
The dust and
sundries caused
during installation are
removed?
It may cause malfunction or
damaging the parts.
11
The gas valve and liquid
valve of connection pipe
are open completely?
It may cause insufficient cooling
(heating) capacity.
12
Is the inlet and outlet
of piping hole been
covered?
It may cause insufficient cooling
(heating) capacity or waster
eletricity.
2. Leakage Detection
a. With leakage detector:
Check if there is leakage with leakage detector.
b. With soap water:
If leakage detector is not available, please use soap water
for leakage detection. Apply soap water at the suspected
position and keep the soap water for more than 3min. If
there are air bubbles coming out of this position, theres a
leakage.
2
.8 CHECK AFTER INSTALLATION
AND TEST OPERATION
1. Check after Installation
Check according to the following requirement after finishing
installation.
No. Items to be checked
Possible malfunction
1
Has the unit been
installed firmly?
The unit may drop, shake or
emit noise.
2
Have you done the
refrigerant leakage test?
It may cause insufficient
cooling (heating) capacity.
3
Is heat insulation of
pipeline sufficient?
It may cause condensation
and water dripping.
4
Is water drained well?
It may cause condensation
and water dripping.
5
Is the voltage of power
supply according to the
voltage marked on the
nameplate?
It may cause malfunction or
damage the parts.
6
Is electric wiring and
pipeline installed
correctly?
It may cause malfunction or
damage the parts.
7
Is the unit grounded
securely?
It may cause electric
leakage.
8
Does the power cord
follow the specification?
It may cause malfunction or
damage the parts.
9
Is there any obstruction
in air inlet and air outlet?
It may cause insufficient
cooling (heating) capacity.
10 The dust and sundries
caused during
installation are removed?
It may cause malfunction or
damaging the parts.
11
The gas valve and liquid
valve of connection pipe
are open completely?
It may cause insufficient
cooling (heating) capacity.
12 Is the inlet and outlet
of piping hole been
covered?
It may cause insufficient
cooling (heating) capacity
or waster eletricity.
2. Test Operation
a. Preparation of test operation
• The client approves the air conditioner installation.
• Specify the important notes for air conditioner to the
client.
b. Method of test operation
• Put through the power, press ON/OFF button on the
remote controller to start operation.
• Press MODE button to select AUTO, COOL, DRY, FAN
and HEAT to check whether the operation is normal or
not.
• If the ambient temperature is lower than 60.8°F, the air
conditioner cant start cooling.