2106026MNAA | XSERIES
G 5
|
137
Figure 11-11: Low range value verification
Adjust the calibrator to apply the high (100%) value of the signal range.
Wait for the value in Current Value to stabilize.
Verify that Current Value displays a value equal or close to the target range high (100%)
value.
Figure 11-12: High range value verification
If all values are correct, calibrate the next AI or click
Close
to exit the Calibration screen.
When calibration for all required AIs successfully completes, remove power from the
controller, remove the calibrator, and reconnect the external device.
If there are errors, proceed to section
11.5.6 Repeat calibration in case of errors
11.5.6
Repeat calibration in case of errors
If the displayed input values are not valid or do not stabilize, the calibration might not be correct. In
Entry mode, the calibrated AI indicates it has been
Field
calibrated regardless of whether the
calibration was successful or not. This procedure sets the AI calibration status back to
Factory
as
required
before repeating the calibration procedures.
To set the AI before repeating the calibration:
Click
Close
to exit calibration.
Click the Entry icon on the PCCU toolbar.
Click
I/O Interface
on the navigation tree. The Analog Inputs tab displays. The calibrated
AI displays Field in the calibration column.
Select
Factory
from the Calibration drop-down list for the appropriate AI.