Factory configuration is the ABB default configuration, or a customer-specific configuration
programmed into the factory folder during final assembly. The factory configuration is read-
only and stored in persistent memory. It can only be updated at the factory.
Startup (cold) configuration is used for a cold restart of the device or when a configuration
package is sent to the device by the PCCU loader. The startup configuration is stored in the
tfCold directory and can be modified or updated as needed.
Running (warm) configuration is used by the device during normal operation. The running
configuration is stored in the tfData directory and can be modified or updated as needed.
1.2.9
Customer data collection files
The customer data collection files contain all the measurement and calculation data the XSeries
G5
generates. These data files are in the tfData directory with the running configuration files. The type
and amount of collection data depends on the number and type of applications active on the
controller.
IMPORTANT NOTE:
The tfData directory also contains trend data for the applications and
calibration files if the controller has been field-calibrated.
1.2.10
Licensing
Device operation requires licensed applications. ABB provides a secure USB flash drive with the
application licenses in the form of credits. Required credits depend on the application type. XSeries
G5
devices ship with the standard applications required for basic system operation (free of charge) and 4
non-removable general credits (included in the base price). Additional general or explicit (custom)
applications require additional credits. Depending on the purchase order, additional application credits
may already be available on the device. Check the credits available on the device. If there are not
enough credits, use the credit key to transfer credits for all required applications. Call the ABB main
office listed on the last page of this manual to purchase additional credits as needed.
IMPORTANT NOTE:
Detailed information on application licensing is included in the PCCU online
help. Select the
Application/ License Management
tab and click
Help
for more information.
IMPORTANT NOTE:
The only program that can write to or read the USB flash drive is PCCU32.
Install the credit key on each available USB port if the same USB port will not be used each time
the credit key is inserted.
To determine if additional credits must be purchased:
Launch PCCU and click
Entry
to connect with the controller in Entry mode.
Click the top item on the navigation tree, then click
Application/License Management
.
The Application/License Management tab displays.
Click
Credit/App Info
to display the Applications Credits Information screen. Locate the
application on the list. Then view and take note of the required credit type for that
application.
Click
Close
. The Application/Licensing Management tab redisplays.
View available and surplus credits in the Device Credits window.
Insert the key USB flash drive in one of the laptop’s USB port
s.
View available credits in the Key Credits window.
If the credits on the device or the key are insufficient or not of the required type, call the ABB to
purchase additional credits. See
on the last page of this manual. Request the specific type
of credit you need and the number of credits.
1.2.11
Additional features
Additional features of the ABB Totalflow system’s flexibility include the following:
Programmable differential pressure no flow cutoff