42/10-55 XU
Temperature Sensor TSHD (SensyTemp Exd)
GB3
Groups
The type examination PTB 99 ATEX 1144 was executed for potentially explosive atmospheres
of group IIC according to EN 50014:1997, EN 50018:1994, EN 50284:1997, and EN 1127-
1:1997.
Temperature class
The devices are normally marked with temperature class T6. Higher operating temperatures
are possible in case of potentially explosive atmospheres permissible for temperature class
T5 or T4. Operating temperature ranges are defined in section 2.3.
2.2
Electrical power limitation
2.2.1 Transmitter with and without indicator
Rated supply voltage
UB
≤
60 V AC
eff
oder 60 V DC
Maximum supply voltage
U
Bmax
= U
B
+ 10%
Maximum thermal / electrical power
P
max
determined according to Table 2-1
(overall power consumption of all electric
components)
Maximum current of power supply
I
max
= P
max
/ U
Bmax
Rated current of fuse
≤
I
max
/ 1,7
Number of electric transmitters/indicators
0 to 2
2.2.2 Measuring inset without transmitter
Rated supply voltage
UB
≤
10 V AC
eff
oder 10 V DC
Maximum supply voltage
U
Bmax
= U
B
+ 10%
Maximum thermal / electrical power
P
max
determined according to Table 2-2 and
Table 2-3 (overall power consumption of all
electric components)
Maximum measuring current of TTDs
below 2 mA each sensor element
Maximum output voltage of TCs
below 100 mV each sensor element
Maximum current of power supply
I
max
= P
max
/ U
Rated current of fuse
≤
I
max
/ 1,7
Number of sensor elements
1 to 3
2.3
Operating temperature range
2.3.1 RTDs and TCs
Lower operating temperature
- 35°C
Upper operating temperature
Connection head AGL, AGLH, AGLHD within zone 1: see Table 2-1
extension tube within zone 1:
see Table 2-1
measuring inset within zone 1:
see Table 2-2
measuring inset with appropriate thermowell or
protection tube within zone 0:
see Table 2-3
2.3.2 Field housings AGLF, AGLFH, AGLFD within zone 1
Lower operating temperature:
- 35°C
Upper operating temperature:
see Table 2-1