41
External auto-reclose start input (input channel 14)
Terminal numbers
X5/9-10
Control voltage range
- I/O module type SPTR 4D1
80…265 V dc
- I/O module type SPTR 4D2
30…80 V dc
Current drain
~2 mA
Contact outputs
Control outputs
X1/3-4, 6-7,
X3/11-12, 13-14, 15-16, 17-18,
X4/11-12, 13-14, 15-16, 17-18,
X5/11-12, 13-14, 15-16, 17-18
- rated voltage
250 V ac or dc
- continuous carry
5 A
- make and carry for 0.5 s
30 A
- make and carry for 3 s
15 A
- breaking capacity for dc, when the control circuit
time constant L/R
≤
40 ms at the control voltage
levels 48/110/220 V dc
5 A/3 A/1 A
- contact material
AgCdO
2
- operating principle when controlled by the
control module
pulse, pulse length 0.1…100 s
Signal outputs
X1/8-9-10,
X2/1-2-3, 4-5-6, 7-8-9,
X6/1-2, 3-4
- rated voltage
250 V ac or dc
- continuous carry
5 A
- make and carry for 0.5 s
10 A
- make and carry for 3 s
8 A
- breaking capacity for dc, when the control circuit
time constant L/R
≤
40 ms at the control voltage
levels 48/110/220 V dc
1 A/0.25 A/0.15 A
- contact material
AgCdO
2
Auxiliary supply voltage
Built-in power supply module type and
permitted supply voltage range
- type SPGU 240A1
80...265 V ac or dc
- type SPGU 48B2
18...80 V dc
Burden of auxiliary supply under quiescent/
operating conditions
~15 W / ~20 W
Overcurrent module SPCJ 3C3
Low-set overcurrent stage I>
- starting current I>, setting range
0.5…2.5 x I
n
- operation modes to be selected
- definite time operation
- operate time t>
0.05…100 s
- inverse definite minimum time (IDMT) mode
acc. to IEC 255-4 and BS 142
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
- time multiplier k
0.05…1.00
High-set overcurrent stage I>>
- starting current I>>, setting range
0.5…20 x I
n
and
∞
- operate time t>>
0.04…100 s