16
Terminal Contact
Function
group
gap
X4
1-2
Input channel 3 of control module, open status (INPUT3/O)
1-3
Input channel 3 of control module, closed status (INPUT3/I)
1-4
Input channel 4 of control module, open status (INPUT4/O)
1-5
Input channel 4 of control module, closed status (INPUT4/I)
6-7
Input channel 10 of control module (INPUT 10) or external auto-
reclose inhibit signal (ARINH)
6-8
Input channel 11 of control module (INPUT 11) or energy pulse counter
9-10
Input channel 13 of control module (INPUT 13)
11-12
Open output 3 of control module (OPEN 3)
13-14
Close output 3 of control module (CLOSE 3)
15-16
Open output 4 of control module (OPEN 4)
17-18
Close output 4 of control module (CLOSE 4)
X5
1-2
Input channel 5 of control module, open status (INPUT5/O)
1-3
Input channel 5 of control module, closed status (INPUT5/I)
1-4
Input channel 6 of control module, open status (INPUT6/O)
1-5
Input channel 6 of control module, closed status (INPUT6/I)
6-7
Input channel 7 of control module, open status (INPUT7/O)
6-8
Input channel 7 of control module, closed status (INPUT7/I)
9-10
Input channel 14 of control module (INPUT 14) or input for external
autoreclose starting signal, not indicated by LED
11-12
Open output 5 of control module (OPEN 5)
13-14
Close output 5 of control module (CLOSE 5)
15-16
Open output 6 of control module (OPEN 6)
17-18
Close output 6 of control module (CLOSE 6)
X6
1-2
Signal output 5 of control module (SIGNAL 5)
3-4
Signal output 6 of control module (SIGNAL 6)
5-6
Not used
7-8
mA input 1 (used only with optional measuring module SPTM 8A1)
9-10
mA input 2 (used only with optional measuring module SPTM 8A1)
Protective earth is connected to its own screw on
the rear panel. The screw is marked with the
earth symbol.
The channel numbers above are equivalent to
those used for setting the control module SPTO
6D3. The following codes are used for the outputs:
Output
Terminal numbers
Output code for inter-
Output code for
locking and configurat.
Direct Output Control
OPEN1
X3/11-12
20
220
CLOSE1
X3/13-14
21
221
OPEN2
X3/15-16
22
222
CLOSE2
X3/17-18
23
223
OPEN3
X4/11-12
24
224
CLOSE3
X4/13-14
25
225
OPEN4
X4/15-16
26
226
CLOSE4
X4/17-18
27
227
OPEN5
X5/11-12
28
228
CLOSE5
X5/13-14
29
229
OPEN6
X5/15-16
30
230
CLOSE6
X5/17-18
31
231
SIGNAL5
X6/1-2
40
40
SIGNAL6
X6/3-4
41
41
Note! When an object is opened and closed, the
OPEN1 and CLOSE1, OPEN2 and CLOSE2
etc. always form pairs, e.g. OPEN1 output is
used to open an object and CLOSE1 output is