13
Low-set neutral overcurrent stage I
ϕ
>
Start current
1...10% x I
n
Start time, typically
150 ms
Operate time, two ranges
0.1...1.0 s and 1.0...10.0 s
Reseting time, typically
100 ms
Drop-off/pick-up ratio, typically
0.95
Operate time accuracy
±
2% of setting or
±
50 ms
Operation accuracy
±
3% of the maximum setting value of
stage I
ϕ
> + inaccuracy caused by
±
1
o
phase
displacement
High-set neutral overcurrent stage I
ϕ
>>
Start current
5...40% x I
n
and
∞
, infinite, or
1...8% x I
n
and
∞
, infinite
Start time, typically
150 ms
Operate time
0.1...1.0 s
Reseting time, typically
100 ms
Drop-off/pick-up ratio, typically
0.95
Operate time accuracy
±
2% of setting or
±
50 ms
Operation accuracy
±
3% of the maximum setting value of
stage I
ϕ
>> + inaccuracy caused by
±
1
o
phase
displacement
Technical data
(modified 2000-02)