35
Data
Channel Code
Data
Values
direction
Direct output control
1…7
O1
W
0=open
1=close
Open select
1…7
V1
RW
0=open
(secured operation)
1=closed
Close select
1…7
V2
RW
0=open
(secured operation)
1=closed
Execute selected open/close
operation
1…7
V3
W
1=execute selected operation
Cancel selected open/close
operation
1…7
V4
W
1=cancel selected operation
Open pulse length
1…7
V5
RW(e) 0.1…100.0 s
Close pulse length
1…7
V6
RW(e) 0.1…100.0 s
Execute selected open/close
operation (common addr. 900)
0
V251
W
1=execute all selected operations
Cancel selected open/close
operation (common addr. 900)
0
V252
W
1=cancel all selected operations
kWh value per pulse
0
S3
RW(e) 0.01…1000 kWh per pulse
Position of switch SG1/2
0
S5
R
0=AR in use (SG1/2=0)
1=AR out of use (SG1/2=1)
Position of switch SG1/1
0
S6
R
0=operation position ( SG1/1=0)
1=interlockings off (SG1/1=1)
Object indication mode
0
S7
RW(e) 0=continuous display
1=automatic switch off
after 10 min.
Display indication mode
0
S8
RW(e) 0=continuous display
1=automatic switch off
after 5 min.
Scaling of current measurement
0
S9
RW(e) 0.00…10000.00 (opt. 1, 2 or 3)
Scaling of voltage measurement
0
S10
RW(e) 0.00…10000.00 (opt. 1, 2 or 3)
Low limit for mA signal of
active power
0
S12
RW(e) -20…+20 mA (opt. 1)
High limit for mA signal of
active power
0
S13
RW(e) -20…+20 mA (opt. 1)
Low limit for mA signal of
react. power
0
S14
RW(e) -20…+20 mA (opt. 1)
High limit for mA signal of
react. power
0
S15
RW(e) -20…+20 mA (opt. 1)
Active power corresponding
to mA signal at low limit
0
S16
RW(e) -999.99…+999.99 MW (opt. 1)
Active power corresponding
to mA signal at high limit
0
S17
RW(e) -999.99…+999.99 MW (opt. 1)
Reactive power corresponding
to mA signal at low limit
0
S18
RW(e) -999.99…+999.99 Mvar (opt. 1)
Reactive power corresponding
to mA signal at high limit
0
S19
RW(e) -999.99…+999.99 Mvar (opt. 1)