16
Data
Code
Data
Values
direct.
Remotely set percentage for the
S21
R, W
0...999%
set start current of stage I
ϕ
>
Remotely set percentage of the
S22
R, W
0...999%
set operate time of stage I
ϕ
>
Remotely set percentage of the
S23
R, W
0...999%
set start current of stage I
ϕ
>>
Remotely set percentage of the
S24
R, W
0...999%
set operate time of stage I
ϕ
>>
Remotely set checksum of
S25
R, W
0...255
switchgroup SG1
Remotely set start current of stage I
ϕ
>
S31
R
1...10% x I
n
Remotely set operate time of stage I
ϕ
>
S32
R
0.1...10 s
Remotely set start current of stage I
ϕ
>>
S33
R
±
1...40% x I
n
±
999 =
∞
Remotely set operate time of stage I
ϕ
>>
S34
R
0.1...1 s
Remotely set checksum of
S35
R
0...255
switchgroup SG1
Maximum recorded value of the
V1
R
±
0...100% x I
n
neutral current I
ϕ
(sign
±
)
±
999, if I
ϕ
> 100% x I
n
Maximum recorded value of the
V2
R
0...25% x U
n
residual voltage U
0
999, if U
0
> 25% x U
n
Number of starts of stage U
0
V3
R
0...255
Number of starts of stage I
ϕ
>
V4
R
0...255
Number of starts of stage I
ϕ
>>
V5
R
0...255
Duration of the latest start event
of stage I
ϕ
>
V6
R
0...100%
Duration of the latest start event
V7
R
0...100%
of stage I
ϕ
>>
Max. recorded value I
0
V8
R
0…100% x I
n
,
999, if I
0
> 100% x I
n
Resetting of output relays and
V101
W
1 = output relays and oper-
operation indicators
ation indicators are reset
Resetting of output relays and
V102
W
1 = output relays and oper-
operation indicators and erasing
ation indicators are reset
of recorded data
and registers (codes
V1…V8) are erased
Remote control of setting values
V150
R, W
0 = setting knobs settings
S11...S15 activated
1 = remote settings S31...S35
activated
Event mask word
V155
R, W
0...255, see chapter
"Event codes"
Self-reset or manual reset mode of
V156
R,W
0…15, see chapter
operation of the LED indicators (SG2)
"Selector switches"
Programming push-buttons (SG3)
V157
R, W
0…7, see chapter
"Selector switches"
Opening of password for the
V160
W
1...999
remote setting procedure
Changing or closing of password
V161
W
0...999
for the remote setting procedure