38
Fault codes
Once the self-supervision system has detected
an internal relay fault, the IRF indicator on the
front panel of the relay module is lit. At the same
time the self-supervision alarm relay that is
normally picked up, drops off. In most situa-
tions a fault code appears on the display of the
relay module. This fault code consists of a red
number one (1) and a green code number that
identifies the fault type. The fault codes should
be recorded and stated when service is ordered.
The table below lists some of the fault codes of
the combined overcurrent and earth-fault relay
module SPCJ 4D28/E351.
Fault code
Type of fault
4
Relay control circuit faulty or missing
30
Read Only Memory (ROM) faulty
50
Random Access Memory (RAM) faulty
51
Parameter memory (EEPROM) faulty, block 1
52
Parameter memory (EEPROM) faulty, block 2
53
Parameter memory (EEPROM) faulty, blocks 1 and 2
54
Parameter memory (EEPROM) faulty, blocks 1 and 2 have different checksums
56
Parameter memory (EEPROM) key faulty. Formatting by writing V167 = 2
195
Too low a value on the reference channel with multiplier 1
131
Too low a value on the reference channel with multiplier 5
67
Too low a value on the reference channel with multiplier 25
203
Too high a value on the reference channel with multiplier 1
139
Too high a value on the reference channel with multiplier 5
75
Too high a value on the reference channel with multiplier 25
252
Filter of I0 channel faulty
253
No interruption from the A/D converter