11
Switch
Function
Factory
default
SGF2/1
Mode of operation of the start indicating code numbers of the differ-
0
SGF2/2
ent stages. When the switches are in position 0, the start indication
0
SGF2/3
code number automatically resets, once the fault disappears. When
0
SGF2/4
the switch is in position 1, the code number remains lit, although the
0
SGF2/5
fault disappears.
0
Switch
Stage
Switch position
Code resets
Code remains
SGF2/1
I>
0
1
SGF2/2
I>>
0
1
SGF2/3
I>>>
0
1
SGF2/4
I
0
>
0
1
SGF2/5
I
0
>>
0
1
SGF2/6
Inhibition of the operation of stage I>>, stage I>>> and stage I
0
>>.
0
SGF2/7
When the operation is inhibited the display shows "- - -", when the
0
SGF2/8
set value is displayed
0
Switch
Stage
Switch position
Not inhibited
Inhibited
SGF2/6
I>>
0
1
SGF2/7
I>>>
0
1
SGF2/8
I
0
>>
0
1
∑
SGF2
0
SGF3/1
Phase discontinuity protection stage
∆
I> to be set out of use.
1
When SGF3/1 = 1, the phase discontinuity protection stage is out
of use. The out of use state is indicated as "- - -" on the display.
SGF3/2
Resetting times of stage I> and I
0
>.
0
SGF3/3
0
SGF3/4
Switch
Stage
Switch position
0
SGF3/5
40 ms
100 ms
500 ms
1000 ms
0
SGF3/2
I>
0
1
0
1
SGF3/3
0
0
1
1
SGF3/4
I
0
>
0
1
0
1
SGF3/5
0
0
1
1
SGF3/6
Inverse time operation of stage I> to be inhibited by the starting of
0
stage I>>.
When SGF3/6 = 1, the inverse time operation is inhibited.
SGF3/7
Inverse time operation of stage I> to be inhibited by the starting of
0
stage I>>>.
When SGF3/7 = 1, the inverse time operation is inhibited.
SGF3/8
Inverse time operation of stage I
0
> to be inhibited by the starting of
0
stage I
0
>>.
When SGF3/8 = 1, the inverse time operation is inhibited.
∑
SGF3
1