34
Outputs
The state information indicates the state of a
signal at a certain moment. The recorded func-
tions indicate such activations of signals, that
happen after the last reset of the registers of the
module. When the value = 0, the signal has not
been activated and when the value = 1, the signal
has been activated.
Output stages
States of the protection stages
State of stage
Recorded
Value
(R)
functions (R)
Starting of stage I>
O1
O21
0 or 1
Tripping of stage I>
O2
O22
0 or 1
Starting of stage I>>
O3
O23
0 or 1
Tripping of stage I>>
O4
O24
0 or 1
Starting of stage I>>>
O5
O25
0 or 1
Tripping of stage I>>>
O6
O26
0 or 1
Starting of stage I
0
>
O7
O27
0 or 1
Tripping of stage I
0
>
O8
O28
0 or 1
Starting of stage I
0
>>
O9
O29
0 or 1
Tripping of stage I
0
>>
O10
O30
0 or 1
Tripping of stage
∆
I>
O11
O31
0 or 1
Output signals
Operation of output signals
State of output
Recorded
Value
(R, W, P)
functions (R)
Output signal SS1
O12
O32
0 or 1
Output signal TS1
O13
O33
0 or 1
Output signal SS2
O14
O34
0 or 1
Output signal TS2
O15
O35
0 or 1
Output signal SS3
O16
O36
0 or 1
Output signal TS3
O17
O37
0 or 1
Output signal SS4
O18
O38
0 or 1
Output signal TS4
O19
O39
0 or 1
Enable of output
O41
0 or 1
signals SS1…TS4