30
Technical data
Feature
Stage I>
Stage I>>
Stage I>>>
Start current
- at definite time
0.5…5.0 x I
n
0.5…40.0 x I
n
and
∞
0.5…40.0 x I
n
and
∞
- at inverse time
0.5…2.5 x I
n
Start time, typ.
70 ms
40 ms
40 ms
Operate time at definite
0.05…300 s
0.04…300 s
0.04…30 s
time characteristic
Time/current characteristic
Extremely inv.
at inverse mode
Very inv.
Normal inv.
Long-time inv.
RI type inv.
RXIDG type inv.
Time multiplier k
0.05…1.0
Reset time, typ.
40 ms
40 ms
40 ms
Retardation time
<30 ms
<30 ms
<30 ms
Reset ratio, typ.
0.96
0.96
0.96
Operate time accuracy
±
2% of set
±
2% of set
±
2% of set
at definite time mode
value or
±
25 ms
value or
±
25 ms
value or
±
25 ms
Accuracy class index E
5
at inverse time mode
Operation accuracy
±
3% of set value
±
3% of set value
±
3% of set value
Feature
Stage I
0
>
Stage I
0
>>
Stage
∆
I>
Start current
0.05…0.8 x I
n
0.05…10.0 x I
n
and
∞
10…100% and
∞
Start time, typ.
70 ms
50 ms
150 ms
Operate time at definite
0.05…300 s
0.05…300 s
1…300 s
time characteristic
Time/current characteristic
Extremely inv.
at inverse mode
Very inv.
Normal inv.
Long-time inv.
RI type inv.
RXIDG type inv.
Time multiplier k
0.05…1.0
Reset time, typ.
40 ms
40 ms
80 ms
Retardation time
<30 ms
<30 ms
Reset ratio, typ.
0.96
0.96
0.90
Operate time accuracy
±
2% of set
±
2% of set
±
2% of set
at definite time mode
value or
±
25 ms
value or
±
25 ms
value or
±
25 ms
Accuracy class index E
5
at inverse time mode
Operation accuracy
±
3% of set value*
±
3% of set value*
±
1 unit
±
3% of
set value
* When the set value is <0.1 x I
n
, the operation accuracy is
±
6.5% of set value.