37
Control parameters
Information
Para-
Data
Value
meter
direction
Resetting of operation indicators and
V101
W
1 = reset perfomed
latched output relay
Resetting of indicators and latched
output relay and clearing of registers
V102
W
1 = reset perfomed
Remote control of setting
V150
R,W
0 = main settings enforced
1 = second settings
enforced
Overcurrent even mask
V155
R,W
0...4096, see section
"Event codes"
Residual/unbalance current event mask
V156
R,W
0...4096, see section
"Event codes"
Output signal event mask
V157
R,W
0...255, see section
"Event codes"
Output signal event mask
V158
R,W
0...1023, see section
"Event codes"
Opening of password for remote setting
V160
W
1...999
Changing and closing of password for
V161
W, P
0...999
remote setting
Activation of self-supervision system
V165
W
1 = self-supervision
system activated
and IRF LED lit
Formatting of EEPROM
V167
W, P
2 = formatting
Fault code
V169
R
0…255
Data communication address of
V200
R,W
1...254
relay module
Data transfer rate
V201
R,W
4800 or 9600 Bd (R)
4.8 or 9.6 kBd (W)
Program version
V205
R
191 A
Reading of event register
L
R
Time, channel number
and event code
Rereading of event register
B
R
Time, channel number
and event code
Type designation of relay module
F
R
SPCJ 4D28
Reading of module state data
C
R
0 = normal state
1 = module been subject
to automatic reset
2 = event register overflow
3 = events 1 and 2 together
Resetting of module state data
C
W
0 = resetting
Time reading and setting
T
R,W
00.000...59.999 s
The maximum capacity of the event register is
65 events. The content of the register can be
read by the L command, 5 events at a time, only
once. Should a fault occur, say, in the data
communication, the B command can be used to
re-read the contents of the register. When
required, the B command can be repeated. In
general, the control data communicator reads
the event data and forwards the information to
an output device. Under normal conditions the
event register of the relay module is empty. The
control data communicator also resets abnor-
mal status data, so this data is normally zero.