Operation, configuration and communication
42/14-39 EN
Sensyflow iG, Version 1.00
47
Submenu level 2
→
TB GAS TEMP MENU
Display indication
Designation according to PA profile
3.0
Explanation
TB TEMP STATE
PRIMARY_VALUE
D
Display of status message for the gas temperature in hexadecimal
notation
Display 0x80 … 0x83
→
OK
(
see section 7.1.2.2
and
see section 7.1.2.3
)
TEMPERATURE UNIT
PRIMARY_VALUE_UNIT
SP
Select from °C, F, K
GAS S1 STATE
SECONDARY_VALUE_1
D
Display of status message for the gas temperature in hexadecimal
notation
Display 0x80 … 0x83
→
OK
(see also section 7.1.2.2 and 7.1.2.3)
HEATER S2 STATE
SECONDARY_VALUE_2
D
Display of status message for the heater temperature in hexadecimal
notation
Display 0x80 … 0x83
→
OK
(
see section 7.1.2.2
and
see section 7.1.2.3
)
SENSOR MEASURING TYPE
SENSOR_MEAS_TYPE
SE
Select from
PV = SV1,
PV = SV2,
PV = SV2 - SV1
(SV1 = gas temperature, SV2 = heater temperature)
ZERO OFFSET COMP GAS
BIAS_1
SP
Input of a zero offset compensation value for the gas temperature in the
selected unit (e. g. -3 °C)
Caution: This function shifts the entire characteristics!
Default = 0
ZERO OFFSET COMP HEATER
BIAS_2
SE
Input of a zero offset compensation value for the heater temperature in
the selected unit (e. g. 5 °C)
Caution: This function shifts the entire characteristics!
Default = 0
END TB GAS TEMP