Operation, configuration and communication
42/14-39 EN
Sensyflow iG, Version 1.00
27
7.1.3
Acyclic data communication (DPV1)
7.1.3.1 Device Management Block
* device-dependant
7.1.3.2 Physical Block
Slot
Index
Relative
index
Parameter
Object
data type
Store
Size
Acc.
Transport
type
Default
value
Mandatory (M)/
Optional (O)
1
0
0
Directory Object
Array,
uint16
C
*
r
a
-
M
1
1
1
Composite_list Dir. Entry/
Array,
uint16
C
*
r
a
-
M
1
2-8
2-8
Directory_continous
Array,
uint16
C
*
r
a
-
O
1
9-13
9-13
Reserved
Slot
Index
Relative
index
Parameter
Object
data type
Store
Size
Access Transport
type
Default value/
allowed range
Mandatory (M)/
Optional (O)
0
16
0
Block Object
DS-32
C
20
r
A
-
M
0
17
1
ST_REV
uint16
N
2
r
A
0
M
0
18
2
TAG_DESC
String
S
32
r,w
A
'
M
0
19
3
Strategy
uint16
S
2
r,w
A
0
M
0
20
4
Alert_Key
uint8
S
1
r,w
A
0
M
0
21
5
Target_Mode
Uint8
S
1
r,w
A
-
M
0
22
6
Mode_BLK
actual
permitted normal
DS-37
D
3
r
A
Block
specific
M
0
23
7
Alarm_SUM
DS-42
D
8
r
A
0,0,0,0
M
0
24
8
SOFTWARE REVISION
String
Cst
16
r
A
-
M
0
25
9
HARDWARE REVISION
String
Cst
16
r
A
-
M
0
26
10
DEVICE MAN ID
Uint16
Cst
2
r
A
#VALUE!
M
0
27
11
DEVICE ID
String
Cst
16
r
A
''-'„iG“
M
0
28
12
DEVICE SER NUM
String
Cst
16
r
A
-
M
0
29
13
DIAGNOSIS
String
D
4
r
A
0
M
0
30
14
DIAGNOSIS EXTENSION
String
D
6
r
A
0
O
0
31
15
DIAGNOSIS MASK
String
Cst
4
r
A
-
M
0
32
16
DIAGNOSIS MASK
EXTENSION
String
Cst
6
r
A
-
O
0
33
17
DEVICE CERTIFICATION
String
Cst
32
r
A
-
O
0
34
18
WRITE LOCKING
Uint16
N
2
r,w
A
2457
O
0
35
19
FACTORY RESET
Uint16
S
2
r,w
A
-
O
0
36
20
DESCRIPTOR
String
S
32
r,w
A
32 blanks
M
0
37
21
DEVICE MESSAGE
String
S
32
r,w
A
32 blanks
M
0
38
22
DEVICE INSTALL DATE
String
S
16
r,w
A
8 blanks
M
0
39
24
IDENT_NUMBER_ SELECTOR Uint8
S
1
r,w
A
1
M
0
40..
26-32
Reserved by PNO
0
32-49
Reserved
0
66
50
Manufacturer
SAP Order No.
String
C
16
r
A
Order-
specific
O
0
67
51
Manufacturer
Default Mask
Uint8
S
1
R/W
A
0
0 .. 4
O