Operation, configuration and communication
46
Sensyflow iG, Version 1.00
42/14-39 EN
Submenu level 2
→
AI FLOW MENU
Display indication
Designation according to
PA profile 3.0
Explanation
AI FLOW STATE
AI FLOW STATE
D
Display of status message for mass flow in hexadecimal notation (status to AI Flow Block)
Display 0x80 … 0x83
→
OK
(
see section 7.1.2.2
and
see section 7.1.2.3
)
FLOW PV_SCALE HIGH
PV_SCALE_HIGH
SE
internal 100 % value, normally upper range value
FLOW PV_SCALE LOW
PV_SCALE_LOW
SE
internal 0 % value, normally lower range value
OUT_SCALE AT 100%
OUT_SCALE_AT 100%
SE
external 100 % value
OUT_SCALE AT 0%
OUT_SCALE_AT 0%
SE
external 0 % value
FLOW FAILSAFE TYPE
FSAFE_TYPE
SP
If the device detects an error by means of the status signal, one of the following two options can be
selected for the output FLOW signal:
LAST VALID VALUE the last valid measuring value
ERROR VALUE the current measuring value
ERROR SUBSTITUTION VALUE a selectable replacement value
FLOW FAILSAFE VALUE
FSAFE_VALUE
SP
Arbitrary numeric value as substitution for an incorrect measuring value. This is only sent to the out-
put if option ERROR SUBSTITUTION VALUE has been selected in FLOW ERROR SIGNAL.
FLOW FILTER FACTOR
PV_FTIME
SP
Filter factor for signal attenuation, adjustable between 0.2 s and 100 s
FLOW HYSTERESIS
ALARM_HYS
SP
Hysteresis for limit value monitoring, input in the selected mass flow unit (e. g. 1 kg/h)
FLOW ALARM HIGH
HI_HI_LIM
SP
Upper alarm limit; alarm is triggered if measuring value exceeds limit
FLOW WARNING HIGH
HI_LIM
SP
Upper warning limit (pre-alarm); warning is issued if measuring value exceeds limit
FLOW WARNING LOW
LO_LIM
SP
Lower warning limit (pre-alarm); warning is issued if measuring value falls below limit
FLOW ALARM LOW
LO_LO_LIM
SP
Lower alarm limit; alarm is triggered if measuring value falls below limit
FLOW SIMULATION
SIMULATE
SP
Outputting FLOW simulation values ON or OFF
(incl. STATUS QUALITY and STATUS LIMIT)
(Note: ON produces the symbol "S" in the display)
FLOW SIMUL. VALUE
SP
Input of the flow simulation value
STATUS QUALITY
SP
Simulation of the STATUS signal, selection from the signals described in section
7.1.2.2
and
7.1.2.3
GOOD OK,
GOOD UPDATE EVENT…
STATUS LIMIT
SP
Simulation of the limit value STATUS, selection between
OK
LOW_LIMIT
HIGH_LIMIT
CONSTANT
END AI FLOW