![ABB RPBA-01 User Manual Download Page 93](http://html.mh-extra.com/html/abb/rpba-01/rpba-01_user-manual_2850093.webp)
DP-V1 communication
93
Example 2b: Writing 2 drive parameters
In this example, the values 300 (12Ch) and 500 (1F4h) are written
to drive parameters 12.02 (4B2h) and 12.03 (4B3h) respectively
using one telegram.
DP
header
5F 01 2F 14 08 02 01 02 10 01 00 04 00 B2
•••
DP-V1 Command
PROFIdrive V3 Parameter Channel
•••
10 01 00 04 00 B3
•••
(Par. Channel continued)
•••
42 01 01 2C
•••
(Par. Channel cont’d)
•••
42 01 01 F4
DP
trailer
(Par. Channel cont’d)
Subindex
Parameter index
Number of elements
Attribute (10h = Value)
Number of parameters
Axis
Request ID (02h = Change Parameter)
Request reference
Data length
Index
Slot number
Function number
Value
Number of values
Format (42h = Word)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]