DP-V1 communication
68
The extended Parameter Data bytes are configured via the
PROFIBUS network configuration tool. The functions are defined
in the GSD file.
SAP 62 (Chk_Cfg)
SAP 62 selects the PPO type to be used. The table below gives
the Hex values that must be sent to the drive to select the PPO
type.
*PKW: “Parameter-Kennung-Wert” (Parameter ID Value)
**PZD: “Prozeßdaten” (Process data)
With PPO1, PPO2 and PPO5, reading/writing parameters is only
possible cyclically through the Parameter Identification (PKW)
channel. With PPO3, PPO4 or PPO6, acyclic parameter
reading/writing is available via the DP-V1 parameter read/write
service.
The PPO type can be changed during runtime. However, the
RPBA-01 will go offline while the configuration is being updated.
27 - 28 0-65536 Fail-safe, PZD8
29 - 30 0-65536 Fail-safe, PZD9
31 - 32 0-65536 Fail-safe, PZD10
Cfg_Data
(Configuration Data)
Type: Octet String - Length: 4 to 28
PPO
Type
Hex
Values
PROFIdrive parameter enabled
*PKW
size in
bytes
**PZD
size in
bytes
1
F3 F1 Acyclic Parameter Read
8
4
2
F3 F5 Acyclic Parameter Read
8
12
3
F1
Acyclic Parameter Read/Write
0
4
4
F5
Acyclic Parameter Read/Write
0
12
5
F3 F9 Acyclic Parameter Read
8
20
6
F9
Acyclic Parameter Read/Write
0
20
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for RPBA-01
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 14: ...Introduction 14 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 38: ...Programming 38 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...