DP-V0 communication
40
Communication start-up
The following Service Access Points (SAPs) are used to initiate
DP communication:
SAP 61 (Set_Prm)
This SAP is used in the parameterisation of the drive.
SAP no.
Short Name Name
0 (Default)
Data_Exch
Transfer Input and Output Data
61
Set_Prm
Send Parameter Data
62
Chk_Cfg
Check Configuration Data
60
Slave_Diag
Read Slave Diagnostic
Prm_Data
(Parameter Data Standard)
Type: Octet String - Length: 8
Byte
Value
Description
0
B8h
Station_Status
1 - 2
Watchdog Factors 1 and 2 (set by the PROFIBUS master)
WdFactor1 × WdFactor2 × 10 ms = monitoring time of the
slave to verify that the master is still active.
3
0Bh
Minimum Station Delay Respond Time
Time after which a slave station is allowed to send response
frames to the master. Calculated by multiplying the Hex
value with t
Bit
(time required for transmitting one bit).
4 - 5
0812h
Vendor Identification (for the RPBA-01: 0812h)
6
00h
Group Identification
Reserved
Sync_Req
Unlock_Req
Lock_Req
Freeze_Req
1 = Slave is requested to process in freeze mode
WD_On
1 = Watchdog on
1 0 1 1 1 0 0 0
00 = Min TSDR and slave-related
parameters may be overwritten
10 = Slave locked for other masters. All
parameters can be carried over
x1 = Slave released for other masters
1 = Slave is requested to process in SYNC mode
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for RPBA-01
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 14: ...Introduction 14 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 38: ...Programming 38 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...