DP-V0 communication
43
SAP 60 (Slave_Diag)
This SAP gives diagnostic information on the slave station.
Diag_Data
(Diagnostic Data)
Type: Octet String - Length: 6 (Standard) + 2 (Extended Diagnosis)
Byte
Description
0
Station_Status_1
1
Station_Status_2
x x x x x x x x
Diag.Station_Non_Existent (Set by Master, reset by Slave)
Slave not found
Diag.Stagion_Not_Ready (Set by Slave)
Slave not ready for data exchange
Diag.Cfg_Fault (Set by Slave)
Received configuration data does not match original configuration data
Diag.Ext_Diag (Set by Slave)
Diagnostic entry present in slave-specific diagnostic area
Diag.Not_Supported (Set by Slave)
Service not supported by slave
Diag.Invalid_Slave_Response (Set by Master, reset by Slave)
Invalid response by slave
Diag.Prm_Fault (Set by Slave)
Invalid parameter or parameter value
Diag.Master_Lock (Set by Master, reset by Slave)
Slave is parameterised by another master
x 0 x x x 1 x x
Diag.Prm_Req (Set by Slave)
Slave requires re-configuration and re-parameterisation
Diag.Stat_Diag (Set by Slave)
Static diagnosis. Slave (temporarily) unable to provide valid
data
Always set to 1 by slave
Diag.WD_On (Set by Slave)
Watchdog on
Diag.Freeze_Mode (Set by Slave)
Freeze command received by slave
Diag.Sync_Mode (Set by Slave)
Sync command received by slave
Reserved
Diag.Deactivated (Set by Master, reset by Slave)
Slave is inacive
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for RPBA-01
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 14: ...Introduction 14 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 38: ...Programming 38 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...