![ABB RPBA-01 User Manual Download Page 53](http://html.mh-extra.com/html/abb/rpba-01/rpba-01_user-manual_2850053.webp)
DP-V0 communication
53
The allocation of data sets, drive parameters and PROFIdrive
parameters to the Parameter Identification part of the PPO type is
shown below. The
Index
column corresponds to the parameter
number (PNU) in the ID part of Parameter Identification. The
Sub-
index
column corresponds to the IND part of Parameter
Identification. The
Example No.
column refers to the examples on
the following pages.
Data set area
Index
Sub-index
Range
(Decimal)
Request Label
Example
No.
0h
1h
1
R/W
6/7
1, 2
0h
2h
2
• • •
0h
63h
99
Drive parameters
Index
Sub-index
Range
(Decimal)
Request Label
Example
No.
0h
65h
101
R/W*
6/7
1, 2
0h
66h
102
• • •
27h
0Fh
9999
*Write access depends on drive parameter type, or operation mode.