DP-V0 communication
51
Parameter handling in cyclic communication (DP)
In cyclic PROFIBUS DP communication, parameter data is
transferred in PPO message types 1, 2 and 5 (see
Figure 6.
). The
Parameter Identification part consists of eight bytes (see below).
The Request Label is used by the master when transmitting data
to the slave, while the Response Label is used by the slave as a
positive or negative acknowledgement. The tables below show the
Request/Response functions.
Request labels (from Master to Slave)
Request Function
Response labels
Ackn. (+) Ackn. (-)
0
No task
0
–
1
Request parameter value
1, 2
7
2
Change parameter value (word)
1
7, 8
3
Change parameter value (double word)
2
7, 8
4
Request description element (not supported) 3
7
5
Change description element (not supported) 3
7, 8
6
Request parameter value (array)
4, 5
7, 8
7
Change parameter value (array word)
4
7, 8
8
Change parameter value (array double word) 5
7,8
9
Request number of array elements
6
7
ID
IND
VALUE
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Request Label
Response Label
*Request Signal
Parameter Number (PNU)
Process Data
Parameter
Identification
*Not used (=0)
CW REF
(PD1, PD2...)
SW ACT
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for RPBA-01
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 14: ...Introduction 14 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 38: ...Programming 38 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...