Quick start-up guide
26
From the PLC programming point, the ABB DRIVES profile is
similar to the Generic profile as shown in the first example.
The start/stop commands and reference are according to the ABB
DRIVES profile. (See the drive manuals for more information.)
If REF1 is used, the reference value ±20000 (decimal)
corresponds to the speed or frequency set by parameter 11.05
(EXT REF1 MAXIMUM) in the forward and reverse directions. If
REF2 is used, whether the limit 11.08 (EXT REF2 MAXIMUM)
corresponds to ±20000 or ±10000 is dependent on the drive type
and/or the application macro selected.
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.