![ABB RMC-100 Startup Manual Download Page 4](http://html1.mh-extra.com/html/abb/rmc-100/rmc-100_startup-manual_3390443004.webp)
4
| 2105551-001 rev. AC
WARNING – Equipment damage.
Potential electrostatic charging
hazard: clean only with damp cloth
2 Site planning and requirements
Installing the RMC requires that customer-supplied enclosures, power sources,
wiring, and location comply with the specifications described in this section.
WARNING – Bodily injury
. Carefully review the specifications listed in
this section to select compliant equipment.
Failure to comply with these specifications may create unsafe
conditions, resulting in bodily injury and equipment damage.
2.1 Enclosure
requirements
The RMC must be installed in an enclosure complying with the following
specifications:
— Enclosure must protect the RMC-100 against shock and impact.
— For Class I, Division 2, or other outdoor installations, the RMC-100 shall be
installed in an enclosure rated at least Type 3R, according to the environment.
— For Class I, Zone 2 installations, the RMC-100 shall be installed inside an
enclosure tested for IP54 in accordance with IEC 60529 and IEC 60079-15.
2.2 Battery and charger requirements
When powering the controller with a battery (battery mode), comply with the
following specifications:
— Battery
specifications:
–
Nominal 12 Vdc Sealed Lead Acid
–
RMC rating for ambient temperature with battery is Ta = -40 °C to +60 °C
(-40 °F to 140 °F)
— Battery charger specifications:
–
Solar panel must be nominal 12 Vdc, 30W or less, or
–
NEC Class 2 power source: 14.5 Vdc to 15.5 Vdc, 1.65 A
WARNING – Bodily injury.
Do not separate when energized, this
applies to all connectors and connections.
Make sure there is no hazardous atmosphere present when performing
maintenance on the unit.
Field wiring cables and wires can be energized from optional power
sources other than the RMC. Disconnecting energized cabling or wiring
would cause a spark that would ignite a hazardous atmosphere if
present.