VOLTAGE = 1.29 kV
•
CURRENT = 20918 A
•
R = 0.89%
•
X=6.42%
•
ROTORANG = -3.04 rad
Note that these values identify a point inside the lens characteristic in zone 1, that is
close to the boundary between zone 1 and zone 2. The START is issued, but no TRIP
is performed.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature of
test sets.
•
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance, that
is a point in the plane R-X which is far away from the lens characteristic. Define the
following three-phase symmetrical quantities (the phase angle is related to phase L1):
V
V
V
V
V
ts
t RZ
VT s
VT p
=
×
×
=
×
×
=
0 9
0 9 1435
0 1
13 8
9 36
1
.
.
.
.
.
,
,
,
EQUATION14066 V1 EN
(Equation 51)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 52)
frequency of V
ts
= 50 Hz
I
50s
= 0 A
I
tfs
= 0 A
•
State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
V
V
V
V
ts
t RZ
VT s
VT p
=
×
×
=
×
×
=
0 9
0 9 1435
0 1
13 8
9 36
1
.
.
.
.
.
,
,
,
EQUATION14066 V1 EN
(Equation 53)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 54)
frequency of V
ts
= 50 Hz
Section 11
1MRK 511 366-UUS -
Testing functionality by secondary injection
116
Commissioning manual
Summary of Contents for RES670 2.1
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Commissioning manual ...
Page 2: ......
Page 14: ...8 ...
Page 56: ...50 ...
Page 60: ...54 ...
Page 68: ...62 ...
Page 86: ...80 ...
Page 102: ...96 ...
Page 178: ...172 ...
Page 200: ...194 ...
Page 201: ...195 ...