A new recording begins. The view is updated if you leave the menu and return.
1.2. Navigate to
General information
or to
Trip values
to obtain more detailed
information.
2. Open the Disturbance handling tool for the IED in the plant structure in PCM600.
2.1. Right-click and select
Execute manual Trig
in the window
Available
recordings in IED
.
2.2. Read the required recordings from the IED.
2.3. Refresh the window
Recordings
and select a recording.
2.4. Right-click and select
Create Report
or
Open With
to export the recordings to
any disturbance analyzing tool that can handle Comtrade formatted files.
Evaluation of the results from the disturbance recording function requires access to a PC
either permanently connected to the IED or temporarily connected to the Ethernet port
(RJ-45) on the front. The PCM600 software package must be installed in the PC.
Disturbance upload can be performed by the use of PCM600 or by any third party tool with
IEC 61850 protocol. Reports can automatically be generated from PCM600. Disturbance
files can be analyzed by any tool reading Comtrade formatted disturbance files.
It could be useful to have a printer for hard copies. The correct start criteria and behavior
of the disturbance recording function can be checked when IED protective functions are
tested.
When the IED is brought into normal service it is recommended to delete all recordings,
made during commissioning to avoid confusion in future fault analysis.
All recordings in the IED can be deleted in two ways:
1. in the local HMI under
Main menu/Clear/Reset disturbances
, or
2. in the Disturbance handling tool in PCM600 by selecting
Delete all recordings in the
IED...
in the window
Available Recordings in IED
.
11.1.4
Event recorder (ER) and Event list (EL)
The result from the event recorder and event list can be viewed on the local HMI or, after
upload, in PCM600 as follows:
1. on the local HMI under
Main menu/Events
, or in more details via
2. the
Event Viewer
in PCM600.
The internal FIFO register of all events will appear when the event viewer is
launched.
Section 11
1MRK 511 366-UUS -
Testing functionality by secondary injection
98
Commissioning manual
Summary of Contents for RES670 2.1
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Commissioning manual ...
Page 2: ......
Page 14: ...8 ...
Page 56: ...50 ...
Page 60: ...54 ...
Page 68: ...62 ...
Page 86: ...80 ...
Page 102: ...96 ...
Page 178: ...172 ...
Page 200: ...194 ...
Page 201: ...195 ...