Verifying the settings by secondary injection
It is advised to connect the analog output channels of the function block OOSPPAM to the
internal disturbance recorder (and in particular to the function block A4RADR) in order
to perform a better analysis of the tests.
If the device is in test mode, the recording of the disturbances are enabled by the setting in
Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DisturbanceReport/DRPRDRE:1:
set the parameter
OpModeTest
to
On
.
1. Check the Application Configuration: verify that hardware voltage and current
channels of the IED are properly connected to SMAI function blocks, and that the
proper analog outputs of SMAI’s are connected to the analog inputs of the function
block OOSPPAM.
2. Connect three-phase voltage channels of the test set to the appropriate IED terminals.
3. Connect in parallel two groups of three-phase currents of the test set to the appropriate
IED terminals.
4. Connect the appropriate trip output of the IED to the input channel of the test set that
monitors the trip.
5. Go to
Main menu/Settings/IED Settings/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1
, and make sure that the function is
enabled, that is,
Operation
is set to
On
.
11.3.2.2
Test of point RE (R
FwdR
, X
FwdX
)
The trajectory of the impedance does not enter the lens characteristic.
Preliminary steady state test at 50 Hz
•
Go to
Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs
to check the available
service values of the function block OOSPPAM.
•
Apply the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
V
V
V
V
ts
t FwdZ
VT s
VT p
=
×
×
=
×
×
=
1 1
1 1 11931
0 1
13 8
95 1
.
.
.
.
.
,
,
,
EQUATION14057 V1 EN
(Equation 17)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 18)
frequency of V
ts
= 50 Hz
Section 11
1MRK 511 366-UUS -
Testing functionality by secondary injection
108
Commissioning manual
Summary of Contents for RES670 2.1
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Commissioning manual ...
Page 2: ......
Page 14: ...8 ...
Page 56: ...50 ...
Page 60: ...54 ...
Page 68: ...62 ...
Page 86: ...80 ...
Page 102: ...96 ...
Page 178: ...172 ...
Page 200: ...194 ...
Page 201: ...195 ...