DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
LORs
v1_dSPC
Oper.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.T
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Test
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Check
CO
-
-
Cmd
Command parameter for
IEC61850
TmpLO
v1_dSPS
stVal
ST
-
TEMP_LO
Mon
Temperature above lockout level
q
ST
-
TEMP_LO
Mon
Quality: Temperature above
lockout level
t
ST
-
TEMP_LO
Mon
Timestamp: Temperature above
lockout level
7.8.3
Insulation medium supervision (liquid) SIML
7.8.3.1
Liquid medium supervision SSIML
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
PID-3706-LOGICALNODEDATA v3
LN type
LN prefix LN class Function block name
SSIML (revision 0) S
SIML
SSIML
Table 29:
SSIML Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter for 61850
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter for 61850
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter for 61850
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter for 61850
Oper.T
CO
-
Mod
Cmd
Mode parameter for 61850
Oper.Test
CO
-
Mod
Cmd
Mode parameter for 61850
Oper.Check
CO
-
Mod
Cmd
Mode parameter for 61850
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter
for 61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
Table continues on next page
1MRK 511 440-UEN A
Section 7
Logical node data model
Switchgear control unit SAM600-IO Version 2.2 IEC
75
Communication protocol manual
Summary of Contents for Relion SAM600-IO
Page 2: ......
Page 10: ...4 ...
Page 20: ...14 ...
Page 40: ...34 ...
Page 88: ...82 ...
Page 92: ...86 ...
Page 96: ...90 ...
Page 106: ...100 ...
Page 107: ...101 ...