![ABB Relion SAM600-IO Protocol Manual Download Page 72](http://html.mh-extra.com/html/abb/relion-sam600-io/relion-sam600-io_protocol-manual_2831072.webp)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
AnIn
a_dMV
t
MX
-
VALUE
Mon
Timestamp: Magnitude of
deadband value
subEna
SV
-
-
-
Enable substitution
db
CF
-
MV db
-
Cycl: Report interval (s), Db: In %
of range, Int Db: In %s
zeroDb
CF
-
MV zeroDb
-
Zero point clamping in 0,001% of
range
7.7.1.9
Trip matrix logic TMAGAPC
IP15121-1 v4
PID-4125-LOGICALNODEDATA v2
LN type
LN prefix LN class Function block name
TMAGGIO (revision 0) TMA
GGIO
TMAGAPC
Table 25:
TMAGAPC Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
aINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter
Oper.T
CO
-
Mod
Cmd
Mode parameter
Oper.Test
CO
-
Mod
Cmd
Mode parameter
Oper.Check
CO
-
Mod
Cmd
Mode parameter
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter
for 61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Beh
aINS
stVal
ST
-
Beh
Mon
Behaviour parameter
q
ST
-
Beh
Mon
Quality: Behaviour parameter
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
Out1
v1SPS
stVal
ST
-
OUTPUT1
Mon
OR function betweeen inputs 1 to
16
q
ST
-
OUTPUT1
Mon
Quality: OR function betweeen
inputs 1 to 16
t
ST
-
OUTPUT1
Mon
Timestamp: OR function
betweeen inputs 1 to 16
Out2
v1SPS
stVal
ST
-
OUTPUT2
Mon
OR function between inputs 17 to
32
q
ST
-
OUTPUT2
Mon
Quality: OR function between
inputs 17 to 32
Table continues on next page
Section 7
1MRK 511 440-UEN A
Logical node data model
66
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual