![ABB Relion SAM600-IO Protocol Manual Download Page 74](http://html.mh-extra.com/html/abb/relion-sam600-io/relion-sam600-io_protocol-manual_2831074.webp)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Alm
a_dSPS
t
ST
-
ALARM
Mon
Timestamp: Indicator of the
integrated time has reached the
alarm limit
RsAccTms
v1_dSPC
Oper.ctlVal
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.T
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Test
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Check
CO
-
-
Cmd
Command parameter for
IEC61850
Wrn
v1_dSPS
stVal
ST
-
WARNING
Mon
Indicator of the integrated time
has reached the warning limit
q
ST
-
WARNING
Mon
Quality: Indicator of the integrated
time has reached the warning
limit
t
ST
-
WARNING
Mon
Timestamp: Indicator of the
integrated time has reached the
warning limit
AccTms
v2_dMV
mag.f
MX
-
ACCTIME
Mon
Integrated elapsed time in
seconds
q
MX
-
ACCTIME
Mon
Quality: Integrated elapsed time
in seconds
t
MX
-
ACCTIME
Mon
Timestamp: Integrated elapsed
time in seconds
7.8
Logical nodes for sensors and monitoring
7.8.1
Circuit breaker monitoring SSCBR
7.8.1.1
Breaker monitoring SSCBR
GUID-30A59448-3B80-4298-965D-19E28BB0BBD8 v3
PID-3267-LOGICALNODEDATA v4
LN type
LN prefix LN class Function block name
SSCBR (revision 3) S
SCBR
SSCBR
Section 7
1MRK 511 440-UEN A
Logical node data model
68
Switchgear control unit SAM600-IO Version 2.2 IEC