Table 5:
BTIGAPC Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter
Oper.T
CO
-
Mod
Cmd
Mode parameter
Oper.Test
CO
-
Mod
Cmd
Mode parameter
Oper.Check
CO
-
Mod
Cmd
Mode parameter
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter
for 61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter
q
ST
-
Beh
Mon
Quality: Behaviour parameter
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
OutInt
b_dINS
stVal
ST
-
OUT
Mon
Output value
q
ST
-
OUT
Mon
Quality: Output value
t
ST
-
OUT
Mon
Timestamp: Output value
7.4
Logical nodes for protection functions
7.4.1
Protection trip conditioning PTRC
7.4.1.1
Logic for group alarm ALMCALH
PID-6510-LOGICALNODEDATA v1
LN type
LN prefix LN class Function block name
ALMCALH (revision 1) ALM
CALH
ALMCALH
Table 6:
ALMCALH Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orCat
CO
-
Mod
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
Mod
Cmd
Mode parameter
Oper.ctlNum
CO
-
Mod
Cmd
Mode parameter
Oper.T
CO
-
Mod
Cmd
Mode parameter
Table continues on next page
1MRK 511 440-UEN A
Section 7
Logical node data model
Switchgear control unit SAM600-IO Version 2.2 IEC
43
Communication protocol manual
Summary of Contents for Relion SAM600-IO
Page 2: ......
Page 10: ...4 ...
Page 20: ...14 ...
Page 40: ...34 ...
Page 88: ...82 ...
Page 92: ...86 ...
Page 96: ...90 ...
Page 106: ...100 ...
Page 107: ...101 ...