GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5
Table 82. Fuse failure supervision VDSPVC
Function
Range or value
Accuracy
Operate value, block of main fuse failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
Operate time, block of main fuse failure at 1 x U
r
to 0
Min. = 5 ms
–
Max. = 15 ms
Reset time, block of main fuse failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
Operate value, alarm for pilot fuse failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
–
Operate time, alarm for pilot fuse failure at 1 x U
r
to 0 Min. = 5 ms
–
Max. = 15 ms
Reset time, alarm for pilot fuse failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB