Injection equipment
GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v3
Table 31. Electromagnetic compatibility tests
Test
Type test values
Reference standards
1 MHz burst disturbance
2.5 kV
IEC 60255-26
100 kHz slow damped oscillatory wave immunity test
2.5 kV
IEC 61000-4-18, Class III
Surge withstand capability test
2.5 kV, oscillatory
4.0 kV, fast transient
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
IEC 61000-4-2, Class IV
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.3
Fast transient disturbance test
4 kV
IEC 60255-26, Zone A
Surge immunity test
1-2 kV, and 2-4 kV, 1.2/50 µs
High energy
IEC 60255-26, Zone A
Power frequency immunity test
150-300 V, 50 Hz
IEC 60255-26, Zone A
Power frequency magnetic field test
1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8
Radiated electromagnetic field disturbance test
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic field disturbance test
20 V/m, 80-1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic field disturbance test
10 V, 0.15-80 MHz
IEC 60255-26
Voltage dips and short interruptions
Dips:
40% /200 ms
70% /500 ms
Interruptions:
0-50 ms: No restart
0… ∞ s: Correct behaviour at
power down
IEC 60255-26
Radiated emission
30-1000 MHz
IEC 60255-26
Conducted emission
0.15-30 MHz
IEC 60255-26
Table 32. Insulation tests, REX060, REX062 and REG670
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min
IEC 60255-27
Impulse voltage test
5.0 kV, 1.2/50 µs, 0.5 J
IEC 60255-27
Insulation resistance
>100 MΩ at 500V DC
IEC 60255-27
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
58
ABB