M12700-1 v4
Table 136. Event list
Function
Value
Buffer capacity
Maximum number of events in the list
1000
Resolution
1 ms
Accuracy
Depending on time synchronizing
M13765-1 v5
Table 137. Indications
Function
Value
Buffer capacity
Maximum number of indications presented for single disturbance
352
Maximum number of recorded disturbances
100
M12702-1 v4
Table 138. Event recorder
Function
Value
Buffer capacity
Maximum number of events in disturbance report
150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
M13747-1 v5
Table 139. Trip value recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance reports
100
M12384-1 v7
Table 140. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
352
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Table 141. Event counter with limit supervision L4UFCNT
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
104