![ABB relion REF615 Applications Manual Download Page 66](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824066.webp)
The optional autoreclosing function is configured to be initiated by operate signals
from a number of protection stages through the
INIT_1...5
inputs. It is possible to
create individual autoreclose sequences for each input.
The autoreclosing function can be inhibited with the
INHIBIT_RECL
input. By
default, few selected protection function operations are connected to this input. A
control command to the circuit breaker, either local or remote, also blocks the
autoreclosing function via the
CBXCBR1_SELECTED
signal.
The circuit breaker availability for the autoreclosing sequence is expressed with the
CB_READY
input in DARREC1. This signal is not connected in the configuration.
The open command from the autorecloser is connected directly to binary output
X100:PO3, whereas the close command is connected directly to binary output
X100:PO1.
Set the parameters for DARREC1 properly.
Check the initialization signals of DARREC1.
DARREC1
INIT_1
INIT_2
INIT_3
INIT_4
INIT_5
INIT_6
DEL_INIT_2
DEL_INIT_3
DEL_INIT_4
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
INHIBIT_RECL
RECL_ON
SYNC
OPEN_CB
CLOSE_CB
CMD_WAIT
INPRO
LOCKED
PROT_CRD
UNSUC_RECL
AR_ON
READY
ACTIVE
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR
B1
B2
O
X120_BI3_CB_OPENED
DARREC1_OPEN_CB
DARREC1_CLOSE_CB
PHIPTOC1_OPERATE
PHHPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
NSPTOC2_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
INTRPTEF1_OPERATE
PDNSPTOC1_OPERATE
DEFHPDEF1_OPERATE
DEFLPDEF2_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
CBXCBR1_SELECTED
DARREC1_INPRO
DARREC1_UNSUC_RECL
GUID-4F81507A-B5DF-4FCD-A5F4-B51E9E683345 V1 EN
Figure 30:
Autoreclosing function
Section 3
1MRS756378 S
REF615 standard configurations
60
REF615
Application Manual
Summary of Contents for relion REF615
Page 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Page 2: ......
Page 22: ...16 ...
Page 398: ...392 ...
Page 402: ...396 ...
Page 403: ...397 ...