EFHPTOC1
BLOCK
ENA_MULT
OPERATE
START
EFLPTOC1
BLOCK
ENA_MULT
OPERATE
START
EFIPTOC1
BLOCK
ENA_MULT
OPERATE
START
EFLPTOC2
BLOCK
ENA_MULT
OPERATE
START
OR6
B1
B2
B3
B4
B5
B6
O
EFLPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
EFIPTOC1_OPERATE
EFLPTOC2_OPERATE
EFLPTOC2_OPERATE
EFLPTOC1_START
EFLPTOC2_START
EFHPTOC1_START
EFIPTOC1_START
EFxPTOC_OPERATE
GUID-15DB4C4F-9B2C-483D-A066-6011F8535402 V1 EN
Figure 338:
Earth-fault protection function
Phase discontinuity protection PDNSPTOC1 protects for interruptions in the normal
three-phase load supply. For example, in downed conductor situations the function is
blocked in case of detection of a failure in secondary circuit of current transformer.
PDNSPTOC1
BLOCK
OPERATE
START
PDNSPTOC1_OPERATE
PDNSPTOC1_START
CCSPVC1_FAIL
GUID-816DE51C-0F1F-4CD9-AA1B-8D88BB8490D7 V2 EN
Figure 339:
Phase discontinuity protection function
Circuit breaker failure protection CCBRBRF1 is initiated via the
START
input by
number of different protection functions available in the IED. The breaker-failure
protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents.
The circuit breaker failure protection function has two operating outputs:
TRRET
and
TRBU
. The
TRRET
operate output is used for retripping its own breaker through
TRPPTRC2_TRIP
. The
TRBU
output is used to give a backup trip to the breaker
feeding upstream. For this purpose, the
TRBU
operate output signal is connected to the
binary output X100:PO2.
Section 3
1MRS756378 S
REF615 standard configurations
234
REF615
Application Manual
Summary of Contents for relion REF615
Page 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Page 2: ......
Page 22: ...16 ...
Page 398: ...392 ...
Page 402: ...396 ...
Page 403: ...397 ...