CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
CBXCBR1_ENA_CLOSE
CBXCBR1_EXE_CL
CBXCBR1_EXE_OP
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
CBXCBR1_SELECTED
GUID-8C73B177-754E-4AD7-9897-C78E6D2C02ED V2 EN
Figure 114:
Circuit breaker control logic: Circuit breaker 1
OR
B1
B2
O
CB_CLOSE_COMMAND
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-8409FB29-60F4-418E-9E13-DE218B4FB87B V1 EN
Figure 115:
Circuit breaker control logic: Signal for closing of circuit breaker 1
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMAND
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-DEB21767-B0D9-4A3B-8601-8C108AE0B706 V1 EN
Figure 116:
Circuit breaker control logic: Signal for opening of circuit breaker 1
AND
B1
B2
O
NOT
IN
OUT
NOT
IN
OUT
TRPPTRC2_TRIP
CBXCBR1_ENA_CLOSE
TRPPTRC1_TRIP
GUID-860F40F5-18B2-48E3-B38F-7225A5F04449 V1 EN
Figure 117:
Circuit breaker close enable logic
The configuration includes logic for generating circuit breaker external closing and
opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect any additional signal applicable for the configuration for
closing and opening of circuit breaker in local or remote mode.
Section 3
1MRS756378 S
REF615 standard configurations
110
REF615
Application Manual