blocked by the master trip TRPPTRC1 and TRPPTRC2 and the circuit breaker open
signal.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-58DD6776-004D-4B7C-8F75-A68BBA22EE1D V1 EN
Figure 194:
Trip circuit supervision function
OR6
B1
B2
B3
B4
B5
B6
O
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
TRPPTRC1_TRIP
TCSSCBR_BLOCKING
GUID-551738DE-408E-4244-861F-335A3D86A8DA V1 EN
Figure 195:
Logic for blocking of trip circuit supervision function
3.7.3.4
Functional diagrams for control and interlocking
Two types of disconnector and earthing switch function blocks are available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration. The disconnector (CB truck) and line side earthing switch
status information is connected to DCSXSWI1 and ESSXSI1.
DCSXSWI1
POSOPEN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
DCSXSWI1_OKPOS
X110_BI6_CB_TRUCK_IN_TEST
X110_BI5_CB_TRUCK_IN_SERVICE
GUID-7EE30E79-0EE5-4765-A882-92BE768FB3DB V1 EN
Figure 196:
Disconnector 1
Section 3
1MRS756378 S
REF615 standard configurations
156
REF615
Application Manual