3.13.2.2
Default disturbance recorder settings
Table 64:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
5
U1
6
U2
7
U3
8
-
9
-
10
-
11
-
12
-
Table 65:
Default disturbance recorder binary channels
Channel
ID text
Level trigger mode
1
DPHLPDOC1 - start
Positive or Rising
2
DPHLPDOC2 - start
Positive or Rising
3
DPHHPDOC1 - start
Positive or Rising
4
PHIPTOC1 - start
Positive or Rising
5
NSPTOC1 - start
Positive or Rising
6
NSPTOC2 - start
Positive or Rising
7
DEFLPDEF1 - start
Positive or Rising
EFPADM1 - start
WPWDE1 - start
8
DEFLPDEF2 - start
Positive or Rising
EFPADM2 - start
WPWDE2 - start
9
EFPADM3 - start
Positive or Rising
WPWDE3 - start
10
INTRPTEF1 - start
Positive or Rising
11
EFHPTOC1 - start
Positive or Rising
12
PDNSPTOC1 - start
Positive or Rising
13
T1PTTR1 - start
Positive or Rising
14
PHPTOV1 - start
Positive or Rising
15
PHPTOV2 - start
Positive or Rising
16
PHPTOV3 - start
Positive or Rising
Table continues on next page
1MRS756378 S
Section 3
REF615 standard configurations
REF615
325
Application Manual
Summary of Contents for relion REF615