Figure 17:
Example characteristic
Non-directional earth fault current protection
Procedure
1.
Measure that the operate current is equal to the
INNonDir>
setting.
The function activates the START and STDIRIN output.
2.
Measure the operate time of the timer by injecting a current of 200% of the
operate value.
3.
Compare the result with the expected value.
The expected value depends on whether definite time
tINNonDir
or inverse time
was selected.
4.
Continue to test another function or complete the test by setting the test mode to
Off
.
Residual overvoltage release and protection
Procedure
1.
Measure that the operate voltage is equal to the
UN>
setting.
The function activates the START and STUN signals.
2.
Measure the operate time by injecting a voltage 1.2 times set
UN>
operate value.
3.
Compare the result with the set
tUN
operate value.
4.
Inject a voltage 0.8 ·
UNRel>
and a current high enough to operate the
directional function at the chosen angle.
5.
Increase the voltage until the directional function is released.
6.
Compare the measured value with the set
UNRel>
operate value.
Section 10
1MRK 511 360-UEN A
Testing functionality by secondary injection
96
Bay control REC670 2.1 IEC
Commissioning manual