DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
EndPosR
a_dSPS
t
ST
-
-
Mon
Timestamp: Indication of extreme
raise position caused blocking
TapChg
b_dBSC
valWTr.posVal
ST
-
-
Mon
Tap position status for IEC61850
mapping
valWTr.transInd
ST
-
-
Mon
Tap changer operating status for
IEC61850 mapping
q
ST
-
-
Mon
Quality: Tap position status for
IEC61850 mapping
t
ST
-
-
Mon
Timestamp: Tap position status for
IEC61850 mapping
Mod
c_dINC
stVal
ST
-
-
Mon
Mode status value parameter for
61850
q
ST
-
-
Mon
Quality: Mode status value
parameter for 61850
t
ST
-
-
Mon
Timestamp: Mode status value
parameter for 61850
7.3
Logical nodes for control
7.3.1
Bay control CBAY
LN type
LN prefix LN class Function block name
QCCBAY (revision 0) QC
CBAY
QCCBAY
Table 7:
QCCBAY Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
-
Cmd
Mode parameter
Oper.origin.orCat
CO
-
-
Cmd
Mode parameter
Oper.origin.orIdent
CO
-
-
Cmd
Mode parameter
Oper.ctlNum
CO
-
-
Cmd
Mode parameter
Oper.T
CO
-
-
Cmd
Mode parameter
Oper.Test
CO
-
-
Cmd
Mode parameter
Oper.Check
CO
-
-
Cmd
Mode parameter
stVal
ST
-
-
Mon
Mode status parameter for 61850
q
ST
-
-
Mon
Quality: Mode status parameter for
61850
t
ST
-
-
Mon
Timestamp: Mode status
parameter for 61850
Beh
a_dINS
stVal
ST
-
Beh
Mon
q
ST
-
Beh
Mon
Quality:
Table continues on next page
1MRS756793 E
Section 7
Logical node data model
630 series
45