DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
BatHi
a_dSPS
stVal
ST
-
ST_UHIGH
Mon
Start signal when battery voltage
exceeds upper limit
q
ST
-
ST_UHIGH
Mon
Quality: Start signal when battery
voltage exceeds upper limit
t
ST
-
ST_UHIGH
Mon
Timestamp: Start signal when
battery voltage exceeds upper
limit
BatLo
a_dSPS
stVal
ST
-
ST_ULOW
Mon
Start signal when battery voltage
drops below lower limit
q
ST
-
ST_ULOW
Mon
Quality: Start signal when battery
voltage drops below lower limit
t
ST
-
ST_ULOW
Mon
Timestamp: Start signal when
battery voltage drops below lower
limit
Vol
b_dMV
mag.f
MX
-
U_BATT
Mon
Service value of the battery
terminal voltage
q
MX
-
U_BATT
Mon
Quality: Service value of the
battery terminal voltage
t
MX
-
U_BATT
Mon
Timestamp: Service value of the
battery terminal voltage
OpBatLo
v1_dSPS
stVal
ST
-
AL_ULOW
Mon
Alarm when voltage has been
below lower limit for a set time
q
ST
-
AL_ULOW
Mon
Quality: Alarm when voltage has
been below lower limit for a set
time
t
ST
-
AL_ULOW
Mon
Timestamp: Alarm when voltage
has been below lower limit for a set
time
OpBatHi
v1_dSPS
stVal
ST
-
AL_UHIGH
Mon
Alarm when voltage has exceeded
higher limit for a set time
q
ST
-
AL_UHIGH
Mon
Quality: Alarm when voltage has
exceeded higher limit for a set time
t
ST
-
AL_UHIGH
Mon
Timestamp: Alarm when voltage
has exceeded higher limit for a set
time
7.12
Logical nodes for power quality events
7.12.1
Voltage variation QVVR
LN type
LN prefix LN class Function block name
PHQVVR instance 1 (revision 0)
PH
QVVR
PHQVVR
QVV1MSTA instance 1 (revision 0) QVV1
MSTA
PHQVVR
QVVMSTA instance 2 (revision 0)
QVV
MSTA
PHQVVR
QVVMSTA instance 3 (revision 0)
QVV
MSTA
PHQVVR
RSLLN0 instance 1 (revision 0)
-
LLN0
PHQVVR
Section 7
1MRS756793 E
Logical node data model
280
630 series
Communication Protocol Manual