DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Beh
a_dINS
q
ST
-
Beh
Mon
Quality: Behaviour parameter for
61850
t
ST
-
Beh
Mon
Timestamp: Behaviour parameter
for 61850
OpTmRs
a_dSPC
Oper.ctlVal
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.T
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Test
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.Check
CO
-
-
Cmd
Command parameter for
IEC61850
stVal
ST
-
-
Mon
Reset command activated (signal
for 61850 mapping)
q
ST
-
-
Mon
Quality: Reset command activated
(signal for 61850 mapping)
t
ST
-
-
Mon
Timestamp: Reset command
activated (signal for 61850
mapping)
OpTmWrn
a_dSPS
stVal
ST
-
WARNING
Mon
Warning accumulated operation
time exceeds Warning value
q
ST
-
WARNING
Mon
Quality: Warning accumulated
operation time exceeds Warning
value
t
ST
-
WARNING
Mon
Timestamp: Warning accumulated
operation time exceeds Warning
value
OpTmAlm
a_dSPS
stVal
ST
-
ALARM
Mon
Alarm accumulated operation time
exceeds Alarm value
q
ST
-
ALARM
Mon
Quality: Alarm accumulated
operation time exceeds Alarm
value
t
ST
-
ALARM
Mon
Timestamp: Alarm accumulated
operation time exceeds Alarm
value
OpTmh
i_dINS
stVal
ST
-
OPR_TIME
Mon
Accumulated operation time of
machine or equipment
q
ST
-
OPR_TIME
Mon
Quality: Accumulated operation
time of machine or equipment
t
ST
-
OPR_TIME
Mon
Timestamp: Accumulated
operation time of machine or
equipment
1MRS756793 E
Section 7
Logical node data model
630 series
271