I.L. 40-386.4
4-20
OSB Inner Blinder
OS Inner
RT
1.00 - 15.00 OHMS
1.0 - 15.0 OHMS
OSB Outer Blinder
OS Outer
RU
3.00 - 15.00 OHMS
3.00 - 15.00 OHMS
Directional Overcurrent
Dir Type
DIRU
Zero Sequence
Negative Sequ
Dual Polariz
ZSEQ
NSEQ
DUAL
Directional Overcur-
rent Ground Backup
Time Curve Family
(With
Time Delay or Inst. Reset)
GB Type
GBCV
Disabled/CO-2/CO-5/CO-6/CO-7/
CO-8/CO-9/CO-11
(Each w/Reset or
Instant)
OUT/CO-2/5/6/7/8/9
/11 I/R
Ground Backup Pick-
up
GBPickup
GBPU
0.50 - 4.00 Amps
0.500 - 4.00 AMPS
Ground Backup Time
Curves within Family
GBTCurve
GTC
1 - 63
1 - 63
Choice of Directional or
Non-Directional
Ground Backup
GB Dir.
GDIR
Yes/No
YES/NO
Close-Into-Fault Trip
CIF Trip
CIF
CIF Trip
CIF Trip w/delay
No CIF Trip
CF
CFT
OUT
Load Loss Trip
LL Trip
LLT
Yes/FDOG/No
YES/NO/FDOG
Loss of Potential Block
LOP Blk
LOPB
Yes/All/No
YES/NO/ALL
Loss of Current Block
LOI Blk
LOIB
Yes/No
YES/NO
Trip Alarm Seal-In
Trip Alm
AL2S
Seal-In/No Seal-In
YES/NO
Remote Setting
Change Enable
Rem. Set
——
Remote Allowed/No Remote
————
Real Time Clock Set
1. Set Year
2. Set Month
3. Set Day
4. Set Weekday
5. Set Hour
6. Set Minute
Set Time
Year
Month
Day
Weekday
Hours
Minutes
——
Yes/No
1980 - 2079
1 - 12
1 - 31
Sunday through Saturday
0 - 23
0 - 59
————
Setting
Function Field
Value Field
Front
Panel
RCP
Front Panel
RCP
SET