Record the 3 latest tripped faults current or “tSt” for manual trip test.

b.

The records are stored in non-volatile memory.

c.

To clear the entire record database:

Step 1: When the relay is healthy, press [RESET] button to step to most recent trip fault record or [FUNC] digit 

shown “A”.

Step 2: Press [ ] and [ ] buttons simultaneously and hold for 3.5s or the [DATA] show “0”. It will clear the 

entire fault records database.

10.

TECHNICAL DATA

AUXILIARY SUPPLY

RECORDS

DIN330-230A(6).....................184~276 VAC

Fault record....................... 3 latest trip fault current or “tSt”

Rated frequency.....................50Hz or 60Hz 

for manual trip test

VA Rating...............................3 VA typical

Storage.............................. Non-volatile memory

SETTING RANGES

DIGITAL INPUT PORT

Sensitivity adjustment............ 30mA, 50mA, 

Remote reset..................... N.O. Dry contact

0.10~1.00A (step=50mA), 

1.00~10.0A (step=1.00A)

OUTPUT CONTACTS

Delay time adjustment........... Instantaneous, 

Contact rating.................... 5A (NO) / 3A (NC) / AC1

0.1~3.0s (step=0.1s) 

Contact arrangement.........Change over

Number of shots.....................0~30 (step=1)

Expected electrical life.......10,000 at rated current

0=Disable reclose function

Expected mechanical life...5,000,000 operations

Dead time...............................1~500sec (step=1sec)

Persistent fault time............... 0~500sec (step=1sec)

ZERO-PHASE CURRENT TRANSFORMERS

0=Disable

To operate with Mikro's ZCT series of current transformers

Reclaim time.......................... 0~500min (step-1min)

0=Disable

MECHANICAL

Lockout self reset time...........0~200hrs (step=1hour)

Mounting............................Standard 35mm DIN rail 

0=Disable

mounting

Programmable contact...........0~6 (step=1)

Approximate weight........... 0.38kg (excluding ZCT)

INDICATORS

Pre-fault alarm....................... Red indicator

Leakage trip delay time..........Red indicator

Leakage trip........................... 7-segment display and red indicators

Manual test trip...................... 7-segment display and red indicators

ZCT connection fault..............7-segment display and red indicators

Trip records............................7-segment display

Real-time leakage current......7-segment display

11.

CONNECTION DIAGRAM

12.

CASE DIMENSION

DIN330 Self-Reclosing Earth Leakage Relay

User's Manual

A BRIEF OVERVIEW

1.

DESCRIPTION

The DIN330 is microprocessors based earth leakage relay with built in self-reclosing function. 

The earth leakage protection module is designed for measure the low-level current flowing from the live 

part of the installation to the earth in the absent of the insulation fault. A zero phase current transformer 

is connected to the relay and function as the sensor for sensing the leakage current. All conductors of 

the circuit to be protected shall go through the ZCT.

While the  self  reclosing  module  provide  multiple  numbers  of  shots  operation.  It  also  incorporates 

intelligent to differentiate the transient fault or persistent fault.

          

a  -  Trip status indicator

c     Alarm status indicator
d     Increment button
e     Decrement button
f      Reset button
g     Integral test button
h     DP2 indicator

i      DP1 indicator

a

c

d

e

f

g

i

j

k

b

b     Model

-
-

-

-

-

-

-
-
-

h

j      FUNC display

k     DATA display

-

Front

Side

71 mm

20 mm

45 m

m

20 mm

70 mm

85 m

m

30 mm 20 mm 20 mm

TRIP SAFE CONTACT

LOAD

6

2

3

4

5

7

1

8

9

10

11

12

13

14

L

N

AUX

CONTACTOR

MIKRO
ZCT

DIN330

REMOTE
  RESET

The EARTH wire
must not pass
through the ZCT

L1   L2   L3   N                                   PE

PROGRAMMABLE CONTACT